AWG wire gauge chart

AWG numbers run backwards: the bigger the gauge, the thinner the wire. This chart gives each copper gauge's diameter, cross-section and resistance per metre, the metric sizes beside them, and a rough guide to the current each one can carry.

AWG 10 to 30

Resistance is for one metre of solid copper at 20 °C. Count the wire out and back: a load 5 m away has 10 m of wire in its loop.

AWGDiameterAreaResistance per metre
102.59 mm5.26 mm²3.19 mΩ
112.30 mm4.17 mm²4.03 mΩ
122.05 mm3.31 mm²5.08 mΩ
131.83 mm2.62 mm²6.40 mΩ
141.63 mm2.08 mm²8.07 mΩ
151.45 mm1.65 mm²10.2 mΩ
161.29 mm1.31 mm²12.8 mΩ
171.15 mm1.04 mm²16.2 mΩ
181.02 mm0.823 mm²20.4 mΩ
190.91 mm0.653 mm²25.7 mΩ
200.81 mm0.518 mm²32.5 mΩ
210.72 mm0.410 mm²40.9 mΩ
220.64 mm0.326 mm²51.6 mΩ
230.57 mm0.258 mm²65.1 mΩ
240.51 mm0.205 mm²82.1 mΩ
250.45 mm0.162 mm²103 mΩ
260.40 mm0.129 mm²130 mΩ
270.36 mm0.102 mm²165 mΩ
280.32 mm0.081 mm²207 mΩ
290.29 mm0.064 mm²262 mΩ
300.25 mm0.051 mm²330 mΩ

Two handy patterns: every three gauges halves the area and doubles the resistance, and every ten gauges is ten times the area.

Metric cable sizes

Outside North America, cable is sold by its cross-section in mm². The diameter here is for a single solid core; stranded cable of the same size is a little fatter.

SizeDiameterResistance per metreNearest AWG
0.5 mm²0.80 mm33.6 mΩ20
0.75 mm²0.98 mm22.4 mΩ18
1 mm²1.13 mm16.8 mΩ17
1.5 mm²1.38 mm11.2 mΩ15
2.5 mm²1.78 mm6.72 mΩ13
4 mm²2.26 mm4.20 mΩ11
6 mm²2.76 mm2.80 mΩ9

The resistances use copper's resistivity of 0.0168 Ω for a metre of 1 mm² wire, the same figure as the lessons and the calculator. Some published tables use 0.0172, a few percent higher, and copper's resistance rises about 0.4% for every degree it warms up.

How much current?

The current a wire can carry safely depends on its insulation, how hot the room is, whether it's bundled with other wires, and how long it is. Treat these as a cautious starting point for short runs, not a rating:

AWGTypical useA cautious current
28–30Ribbon cable, wire-wrap, signalsUp to about 0.5 A
22–24Breadboard hook-up wire, sensorsUp to about 1 A
18–20LED strips, small motorsUp to about 5 A
1612 V accessories, speaker cableUp to about 10 A
14Mains lighting circuits (USA)15 A
12Mains socket circuits (USA)20 A
10Heavy 12 V runs, battery leads30 A

Flexible mains cords in metric sizes are commonly rated 3 A for 0.5 mm², 6 A for 0.75 mm², 10 A for 1 mm², 16 A for 1.5 mm², 25 A for 2.5 mm² and 32 A for 4 mm².

Picking a wire

  1. Find the current the load draws.
  2. Pick a size from the current table that carries it with room to spare.
  3. Check the voltage drop: resistance per metre × the length out and back × the current.

A 12 V LED strip draws 2 A, 5 m from its supply. In 22 AWG the loop is 10 × 0.0516 = 0.52 Ω, which drops about 1 V: 9% of 12 V, and the far end looks dim. In 16 AWG it's 0.13 Ω and about 0.26 V, 2%. On low voltages the drop, not the heat, usually sets the size.

Free lesson

Now build it yourself

Each lesson comes in three short parts: see the idea, try it on a live board, then build it yourself, with quick checks as you go.

Try it yourself: free lesson

“Lost in the wire” is lesson 4 of 6 in Watt Harbour, Power & Energy World 1. Free with an account. Lessons unlock in order, so you’ll do the 3 before it first.

Or start from the very first lesson, no account needed

Work it out

The ideas behind it

Questions people ask

Why does a bigger AWG number mean a thinner wire?

The numbers began as a count of drawing steps: each pass through a smaller hole made the wire thinner and added one to the gauge. Every three gauges halves the copper: 22 AWG has about half the cross-section of 19 AWG, and twice the resistance.

What is 22 AWG in mm²?

About 0.33 mm², 0.64 mm across. It's the usual solid hook-up wire for breadboards. It has about 52 mΩ per metre, so a metre of it drops about 0.05 V at 1 A.

What size wire do I need for 10 A at 12 V?

For a short run, 16 AWG or 1.5 mm² is a common choice. Over a longer run, check the voltage drop too: a lamp 5 m away has 10 m of wire in its loop, and 10 m of 1.5 mm² drops about 1.1 V at 10 A, 9% of 12 V. Go up to 2.5 or 4 mm².

Is stranded wire the same as solid wire of the same gauge?

It has about the same copper, so about the same resistance, but it's a little fatter and far more flexible. Use solid wire for breadboards and stranded wire for anything that moves or bends.

More charts